The CO2 Extinguishing System is an intelligent automatic extinguishing system consisting of bottle group brackets, storage bottles, container valves, high-pressure hoses, check valves, header pipes, safety valves, distribution pipes, selector valves, and pressure signal devices. It is designed for total flooding extinguishing to protect single or multiple areas. This system features advanced technology, high efficiency, and easy maintenance with three start-up modes: automatic, manual, and mechanical emergency operation.
| Model & Specifications | CO2 Fire Fighting Extinguisher System |
| Volume of Storage Bottle | 70/80L |
| Storage Pressure (20ºC) | 5.7MPa |
| Maximum Working Pressure | 12.4MPa (50ºC) |
| Filling Density | ≤0.60 kg/L |
| Working Start-up Power | DC24V, 1.5A |
| Technical Way | Total Flooding |
| Discharge Time | ≤ 60 S |
| Driving Gas | Nitrogen |
| Ambient Temperature | 0 ºC ~ 50 ºC |
This system is primarily applicable to the following types of fires:
Typical installation environments include computer rooms, data storage rooms, libraries, bank vaults, cable tunnels, printing presses, oil-immersed transformers, and ship cabins.